Home » Case Studies » Smoke and heat in an underground car park
Consultancy study · FDSFire safety engineering study
Smoke and heat in an underground car park
This study examines fire and smoke behaviour in an enclosed underground car park using the Fire Dynamics Simulator (FDS). A single car fire is modelled to assess how jet-fan mechanical ventilation controls smoke, supporting performance-based fire safety design.
- Fire safety
- Smoke control
- Jet fans
- FDS
- LES
- 4 MCartesian cells
- LESFDS turbulence model
- 1car fire with prescribed heat release rate
01 · Set-up
Model, mesh and settings
Mesh and model
| Solver | Fire Dynamics Simulator (FDS) |
|---|---|
| Mesh | Cartesian, about 4 million cells, refined near the fire and jet fans |
| Turbulence | Large eddy simulation |
| Fire source | Car fire with growth, steady and decay phases |
Boundary conditions
| Inlet | Open boundary |
|---|---|
| Outlet | Open exhaust |
| Jet fans | Velocity inlets |
| Walls, floor, ceiling | Adiabatic, no-slip |
| Fire | Prescribed heat release rate |
02 · Results
What the comparison shows
Highlights
- The fire plume first forms a ceiling smoke layer; once the jet fans start, the smoke is pushed along the ceiling towards the exhausts.
- Jet fans limit smoke build-up near the fire and keep the lower levels clearer.
- Velocity contours confirm a continuous longitudinal flow path for smoke extraction.
References
- Deckers, X., Haga, S., Sette, B. and Merci, B. (2012). Smoke control in case of fire in a large car park: full-scale experiments. Fire Safety Journal.
- McGrattan, K., et al. (2008). Fire Dynamics Simulator (Version 5) Technical Reference Guide. NIST Special Publication 1018-5.
- Tilley, N., Deckers, X. and Merci, B. (2012). CFD study of ventilation velocity and smoke back-layering distance in car parks. Fire Safety Journal, 48, 11–20.
- Merci, B. and Shipp, M. (2012). Smoke and heat control for fires in large car parks: lessons learnt from research? Fire Safety Journal.