Shell-and-tube heat exchanger

Pressure drop (ΔP) and thermal performance (LMTD) of a shell-and-tube heat exchanger are analysed with conjugate heat transfer, with shell-side and tube-side water exchanging heat across the tube bundle. Flow and thermal fields are cross-validated between Ansys Fluent and FTL FlowSuite for mass flow rates of 0.5 to 2.5 kg/s on each side.

  • Shell-and-tube heat exchanger
  • Pressure drop
  • LMTD
  • Conjugate heat transfer
Velocity and temperature contours: Ansys Fluent vs FlowSuite
  • 2.2%average deviation in LMTD
  • 3%average deviation in pressure drop
  • 0.5–2.5 kg/sflow rates tested
01 · Set-up

Model, mesh and settings

Simulation set-up

Shell inlet0.5–2.5 kg/s, 293 K
Tube inlet0.5–2.5 kg/s, 313 K
Outlet1 bar
Mesh0.5 million cells
FluidWater (shell and tube side)
Turbulence inletIntensity and hydraulic diameter
Turbulence modelSST k-ω
Simplified model with boundary conditions
02 · Results

What the comparison shows

Highlights

  • Both solvers agree closely in shell-side LMTD (about 2.2% average deviation) and pressure drop (about 3% average deviation) at every flow rate tested.
  • Velocity and temperature fields match closely between the two solvers, confirming consistent thermal and hydraulic predictions.
Shell-side LMTD vs mass flow rate: Ansys Fluent vs FlowSuite
Pressure drop vs mass flow rate: Ansys Fluent vs FlowSuite